When to use this checklist
-
Step 1: Confirm oil level and oil spec
-
Step 2: Match service intervals to running hours, not the calendar
-
Step 3: Check the intake filter—don't just focus on oil
-
Step 4: Watch discharge temperature and differential pressure—these two numbers don't lie
-
Step 5: Confirm the problem isn't downstream, not the compressor itself
-
Step 6: Before you reset, record the fault code and operating conditions
-
Step 7: Know when to call for service, and when not to
-
Common mistakes and things to watch for
When to use this checklist
If you're running a Kaeser compressed air system—screw compressor, dryers, the whole loop—this checklist is for you. It's built for the person who manages the plant room, the facility engineer, or whoever got handed the job of "don't let the compressor break down."
There are 7 steps. Work through them in order.
One caveat upfront: this list covers routine maintenance and most emergency situations. If you're dealing with a controller failure, major airend overhaul, or VFD fault, skip the DIY approach and call an authorized service provider. I've seen several plants across the North Island try to handle those themselves, and small problems turn into big ones fast. The service fee you save is never worth the downtime cost.
That's not an exaggeration. In winter 2023, a food manufacturing plant in Auckland had a compressor trip offline. The duty engineer assumed it was a low-oil issue and topped it up from a drum in the warehouse. Didn't check the spec. Forty-eight hours later, the airend seized. The machine was down for a week, production couldn't wait, and they ended up renting a temporary unit to bridge the gap. That drum was a competitor's product—wrong viscosity, completely incompatible with Kaeser's Sigma Fluid S-460. Honestly, I'm not sure why some facilities treat compressor oil so casually. My best guess is a lot of people think "oil is oil, as long as it lubricates."
It isn't.
Step 1: Confirm oil level and oil spec
Stop the machine. Let the system depressurize. Check the sight glass.
One easy-to-miss point: the oil level just needs to sit near the middle of the sight glass. Don't top up the moment you see it slightly low. Overfilling loads the oil separator and actually drives oil consumption up.
Then check the oil spec. Kaeser machines use specified lubricants. S460 is a common Sigma Fluid grade, but not every Kaeser model takes S460—check your manual. If the machine was bought used or the maintenance log is missing, don't guess. Take a photo of the current oil label, note the machine serial number, and call your Kaeser New Zealand service contact.
This matters more than the oil level itself.
Step 2: Match service intervals to running hours, not the calendar
Service intervals are tracked by hours, not months.
Under standard conditions, synthetic oil typically gets changed every 4,000 to 8,000 hours. Mineral oil runs shorter. New Zealand's climate is relatively dry and humidity is manageable—that's an advantage compared to Southeast Asia. But if your plant is in a dusty environment, or the compressor room has poor ventilation and high ambient temperatures, shorten the interval.
Rather than hunting for a generic "every X thousand hours" number online, look at two things: oil analysis reports and the machine's running log. Oil analysis isn't expensive—usually NZ$150 to NZ$300 per sample as of January 2025—and it tells you oil life remaining, metal wear particles, and moisture content before a problem develops.
If you don't have a log and don't know when the oil was last changed—start one today.
Step 3: Check the intake filter—don't just focus on oil
I'm pulling this out as its own step because too many people fixate on oil and ignore intake and separation.
A blocked intake filter reduces output. If you're only watching the pressure gauge, you might misdiagnose it as "the compressor is failing" when a filter change would solve it. A clogged oil separator raises differential pressure and oil consumption goes abnormal.
Honestly—I made this exact mistake in my first year on the job. I managed one machine, changed the oil religiously, kept meticulous records. Never checked the intake filter. It clogged badly enough that the machine tripped on high temperature. Two days waiting for the part. Embarrassing.
Now my rule is simple: if the panel is open for any inspection, the filters get checked too. It takes five extra minutes.
Step 4: Watch discharge temperature and differential pressure—these two numbers don't lie
Listening for strange noises and glancing at the pressure gauge is guessing.
Normal discharge temperature on a screw compressor is typically in the 70–95°C range, depending on model and ambient conditions. If discharge temp is clearly elevated, it could be a dirty cooler, restricted oil flow, or a faulty thermostatic valve. If the differential between oil pressure and discharge pressure is widening, the oil separator is likely clogged.
My experience: temperature creeping up slowly and differential widening gradually are the changes that get ignored. One glance a day beats one check a week. Write it in the shift log.
Step 5: Confirm the problem isn't downstream, not the compressor itself
Sometimes end-of-line pressure is low—and the problem isn't the compressor at all.
Think of it like a car's AC compressor: when the AC compressor acts up, the symptom might show at one vent blowing warm, but the root cause is elsewhere in the system. Same with compressed air. Dryer, filters, receiver tank, pipe leaks—any link in the chain drags down end-of-line pressure.
Start with the dryer's inlet-to-outlet differential. Check that the drain trap is cycling properly. Walk the piping from the receiver to the point of use and look for leaks. Pipe leaks in plants are extremely common—a walk-through often solves in twenty minutes what would otherwise turn into a compressor teardown.
Step 6: Before you reset, record the fault code and operating conditions
This step is for the emergency scenario.
If the Kaeser controller throws a fault or trips, the first move is not reset—it's record. Fault code, discharge temperature, oil pressure, running hours, what happened right before the trip. Photo or write it down.
Plenty of sites think "a reset fixed it." Then it trips again two days later—and there's nothing in the log. This isn't like figuring out how to reset a Honeywell thermostat with no reset button—every Kaeser model has documented fault codes and a reset procedure. Check the manual. Write down the code.
Record first, then reset. If it trips again after reset, don't keep trying. Call the service provider.
Step 7: Know when to call for service, and when not to
This is the dividing line.
You can handle these yourself: routine oil level checks, filter replacement, condensate draining, filter differential checks. Once you've done them a few times, no service call needed.
Do not attempt these yourself: unusual airend noise, persistent high temperature, oil that turns dark or discolored, repeated controller alarms, VFD faults. Bring in a qualified service provider.
Look—I'm not saying everything requires a paid service visit. Simple routine tasks are fine to do in-house. But when it comes to airends, bearings, and electrical controls, the money you save doing it yourself doesn't compare to the downtime cost when it goes wrong.
Also, Kaeser's service coverage in New Zealand isn't as dense as in Europe. Emergency response time depends on which city you're in. Keep the service contact, machine serial numbers, and maintenance records in one folder—it saves hours when something goes wrong. Same principle as preparing an electric snow blower before winter—if you wait until the day you need it, it's too late.
Common mistakes and things to watch for
A few issues I see over and over, ordered by frequency:
- Using non-specified oil. Saves money at purchase. Costs money everywhere after that. I've seen gummed-up separators, overheating, and airend wear from mismatched oil more times than I can count.
- Watching oil pressure but not discharge temperature. Normal oil pressure doesn't mean the oil circuit is healthy. Discharge temperature is the direct indicator of heat load.
- Running filters until they're completely clogged. Change on differential pressure, not on feel.
- Not writing down maintenance records. The next person has no idea where to pick up.
- Letting small issues become big ones. High-temp trip, reset, move on—that pattern almost always ends in a major overhaul.
This checklist won't cover everything. It covers maybe 70–80% of routine maintenance plus the emergency situations you can reasonably assess yourself. If your machine is an S460 or larger, has significant age, or runs high load—I'd push the oil analysis frequency up. If the machine is approaching its overhaul window, plan it early. Don't wait for a failure.
Planning ahead is always cheaper than responding to an emergency.